Electrical Description
The Intelligent Manual Call Point is loop powered and operates at 17-35V DC for all variants.
Operation
The address of each call point is set at the commissioning stage by means of a DIL switch. A solid red alarm LED is provided on the manual call point. This LED is controlled independently of the call point, by the control panel. The LED will flash yellow if there is a fault and flash green when the device is polled. Discovery and CoreProtocol configurable. Once activated, the Intelligent Manual Call Point can be reset by inserting the reset key into the front facing LED, turning clockwise until a positive click and reset occurs. The Intelligent Manual Call Point incorporates a short circuit isolator which will ensure its operation in the event of a short circuit fault on the loop. Isolator operation is indicated by a solid yellow LED. For further details of the isolator refer to data sheet PP2090, available on request. This manual call point helps reduce installation time as all the initial installation cabling is wired to a removable terminal block which fits neatly in the back of the manual call point.
Mechanical Construction
The component parts of the call point are moulded in a robust fire retardant polycarbonate.
Backward Compatibility
The Intelligent Manual Call Point will operate with compatible Apollo control equipment using the digital XP95, Discovery and CoreProtocols.
EMC Directive 2014/30/EU
The Intelligent Manual Call Point complies with the essential requirements of the EMC Directive 2014/30/EU, provided that it is used as described. A copy of the Declaration of Conformity is available from Apollo on request. Conformity of the Intelligent Manual Call Point with the EMC Directive does not confer compliance with the directive on any apparatus or systems connected to it.
Construction products regulation 305/2011
The Intelligent Manual Call Point complies with the essential requirements of the Construction Products Regulation 305/2011. A copy of the Declaration of Performance is available from Apollo on request.
Product Information
The Intelligent Manual Call Point has been designed for indoor applications and are available in a variety of colours for different applications such as initiating a hazard rather than a fire alarm. The Intelligent Manual Call Point can be used on XP95, Discovery and CoreProtocol systems.