Maximal3FD Access Power Controller distributes and switches power to access control systems and accessories. It converts a 120VAC 60 Hz input into 16 independently controlled 12VDC or 24VDC power-limited PTC protected outputs. The outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control System, Keypad, Push Button, REX PIR, etc. Unit will route power to a variety of access control hardware devices including; Mag Locks, Electric Strikes, Magnetic Door Holders, etc. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the 16 outputs. All interconnecting equipment must be UL Listed.